    1.0 OBJECTIVE

    To lay down the procedure for diesel generator set (DG).

    2.0 SCOPE

    This SOP shall be applicable for diesel generator set in utility block.

    3.0 RESPONSIBILITY

    Officer/Engineer/Executive

    4.0 ACCOUNTABILITY

    Head of Engineering

    5.0 PROCEDURE

    5.1 FOR STARTING DIESEL GENERATOR SET IN MANUAL MODE

    5.1.1 Check fuel level into the diesel service tank.
    5.1.2 Check battery voltage on the alternator panel. It should be 23 to 26 volts DC.
    5.1.3 Check coolant level into the radiator.
    5.1.4 Start lubricating pump by pushing its “ON” button on the breaker panel.
    5.1.5 Release the Red Color Emergency Push button and reset the D.G Set by pressing the Reset Button. Crank the engine by turning the key to “RUN” position.
    5.1.6 Engine will pick up and will develop voltage.
    5.1.7 Check voltages between R-Y, Y-B and B-R. It should be 415 to 420 Volts.
    5.1.8 Check frequency of supply, It should be 49.5 to 50 Hz.
    5.1.9 Now close the D.G. breaker from the alternator panel.
    5.1.10 Use touch screen to scroll the readings.
    5.1.11 Check various readings of parameters on alternator panel and note it in the DG set operation monitoring record.
    5.1.12 The parameters are: RPM, lub oil pressure, lub oil temperature, water temperature (in / out), voltage (RY, YB, BR), current (R, Y, B), frequency, KWH, KW, P.F.

    5.2 FOR STOPPING DIESEL GENERATOR SET IN MANUAL MODE

    5.2.1 Check final readings of parameters and note in the DG Set Log Book.
    5.2.2 By pressing Open Button on the alternator panel release the DG in comer breaker.
    5.2.3 Turn the key of DG set to OFF position.
    5.2.4 Press the red color Emergency push button.

    5.3 FOR STARTING DIESEL GENERATOR SET IN AUTO MODE

    5.3.1 After a power failure, the engine will start automatically after 30 seconds
    5.3.2 Check fuel level into the diesel service tank.
    5.3.3 Check coolant level into the radiator.
    5.3.4 Engine will pick up and will develop voltage.
    5.3.5 Check voltages between R-Y, Y-B and B-R. It should be 415 to 420 Volts.
    5.3.6 Check frequency of supply, It should be 49.5 to 50 Hz.
    5.3.7 D.G. breaker will close automatically.
    5.3.8 Use touch screen to scroll the readings.
    5.3.9 The parameters are: RPM, lub oil pressure lub oil temperature, water temperature (in / out), voltage (RY, YB, BR), current (R, Y, B), frequency, KWH, KW, P.F.

    5.4 FOR STOPPING DIESEL GENERATOR SET IN AUTO MODE

    5.4.1 DG Set verifies the M.S.E.B. Supply is resumed.
    5.4.2 The DG incomer, bus coupler 1 and 2 breakers will open automatically.
    5.4.3 The breakers of transformer 1 and 2 will close automatically.
    5.4.4 Engine will stop automatically.

    6.0 ABBREVIATION

    6.1 SOP: Standard Operating Procedure
    Get editable documentsView List

    3 comments: Post Yours! Read Comment Policy ▼

    1. Very helpful blog. Thanks for sharing such a useful information. DG sets are used in places that have no connection to power grid, and as emergency power-supply if the grid fails.

      ReplyDelete
    2. Very useful information. The vocabulary used is very friendly. Other Items in that SOP can be added such as Reference documents, Risk Association with the process, Flow chart ??

      ReplyDelete
    3. Amazing write up! Thanks for this post

      ReplyDelete

    Please don't spam. Comments having links would not be published.


    Popular Categories ๐Ÿท️

    QA SOPs QC SOPs Micro SOPs HVAC Production SOPs Stores SOPs Checklists Maintenance SOPs HPLC Sterile GLP Validation Protocols Water System GDP Regulatory Maintenance Calibration Warning Letters Education B.Pharmacy
    Online Courses Salary Calculator
    Follow on Whatsapp


    Certificate Courses ๐ŸŽ–️

    Pharmaceutical Courses

    Follow Pharmaguideline


    DOCUMENTS ๐Ÿ“‹

    PHARMACEUTICAL DOCUMENTS




    Editable Pharmaceutical Documents in MS-Word Format. Ready to use SOPs, Protocols, Master Plans, Manuals and more...

    View


    adsbypg


    GET APP FOR NEWS UPDATES


    Android App