    SOP for Measurement of Air Velocity and Calculation of Air Changes per Hour

    Standard operating procedure to measure the air velocity and calculate the air changes fer hour in classified area to maintain the area.

    1.0 OBJECTIVE

    To lay down the procedure for measurement of air velocity and calculation of air changes per hour for classified areas.

    2.0 SCOPE

    This SOP shall be applicable for classified areas and laminar air flow.

    3.0 RESPONSIBILITY

    Officer /Executive/Assistant Manager

    4.0 ACCOUNTABILITY

    Head of Engineering

    5.0 PROCEDURE

    5.1 Ensure that air handling unit is “ON” of that area.
    5.2 Measure the hood /grill size and calculate the area of the hood / grill in sqft.
    5.3 In case of terminal HEPA filters place the calibrated anemometer 6 inches away from the grill at different locations and measure the air velocity in feet per minute.
    5.4 In case of diffusers place the calibrated anemometer at the bottom face of the hood at different locations and measure the air velocity in feet per minute.
    5.5 Calculate the average air velocity of the five locations.
    5.6 Calculate the air quantity in CFM by multiplying the area with average air velocity.
    5.7 Repeat the Step 5.2 to step 5.5 for all supply air diffusers/ grills available in the room.
    5.8 Calculate the total air quantity in CFM inside the room.
    5.9 Calculate the air changes per hour.
    5.10 Record the observations in a format of measurement of air velocity and calculation of air changes.
    5.11 The frequency for measurement of air velocity and calculation of air changes shall be once in a year for classified areas.
    5.12 The frequency for measurement of air velocity for laminar air flow shall be once in a six months and shall be done by an external agency.
    5.12.1 The velocity measurement shall be carried out as per schedule shown.

    5.13 ACCEPTANCE CRITERIA

    5.13.1 The measured air quantity shall not be less than the designed air quantity and the calculated air changes shall not be less than the designed air changes per hour.
    5.13.2 Average air velocity for laminar air flow shall be 90 +/- 20%
    5.14 If the acceptance criteria don’t meet then take the necessary corrective actions and repeat the step 5.3 to step 5.9.

    6.0 ABBREVIATIONS

    6.1 SOP: Standard Operating Procedure
    6.2 CFM: Cubic Feed per Minute
    Get editable documentsView List

    No comments:

    Post a Comment

    Please don't spam. Comments having links would not be published.


    Popular Categories ๐Ÿท️

    QA SOPs QC SOPs Micro SOPs HVAC Production SOPs Stores SOPs Checklists Maintenance SOPs HPLC Sterile GLP Validation Protocols Water System GDP Regulatory Maintenance Calibration Warning Letters Education B.Pharmacy
    Online Courses Salary Calculator
    Follow on Whatsapp


    Certificate Courses ๐ŸŽ–️

    Pharmaceutical Courses

    Follow Pharmaguideline


    DOCUMENTS ๐Ÿ“‹

    PHARMACEUTICAL DOCUMENTS




    Editable Pharmaceutical Documents in MS-Word Format. Ready to use SOPs, Protocols, Master Plans, Manuals and more...

    View


    adsbypg


    GET APP FOR NEWS UPDATES


    Android App