SOP for Conduct Temperature Mapping in Stores | Pharmaguideline
  •   Pharmaguideline Courses Start Learning
  • Apr 17, 2021

    SOP for Conduct Temperature Mapping in Stores

    Standard operating procedure of temperature mapping in stores to identify the location of the worst point at which the thermometer and hygrometer for daily monitoring needs to be placed.

    1.0 OBJECTIVE

    To lay down a procedure for conduct a temperature mapping exercise in store.

    2.0 SCOPE

    This SOP shall be applicable to Cold Storage, Foil Store, BSR and R.M. Store where Raw Materials, Packing Material and Finished Products are stored under specified temperature conditions.

    3.0 RESPONSIBILITY

    Stores Person/ QA Person.

    4.0 ACCOUNTABILITY

    Head of Department

    5.0 PROCEDURE

    5.1 Before starting Temp. Mapping activity, ensure that all respective air handling unit and cold storage should be “ON” for 24 hours, RM Stores seven days, BSR and Foil Store for three days.
    5.2 Place 16 calibrated probes for RM Store, 8 calibrated probes for BSR and Foil Store and 6 calibrated probes for Cold Storage at different places as shown in schematic diagram in a respective area.
    5.3 After appearing stable temperature, start the recording of temp. at every half hours for the respective area and respective days.
    5.4 After completion of the activity, find out the hottest zone in the area and place the thermometer and hygrometer in the respective zone.
    5.5 Record the daily monitoring of temperature and humidity as per the schedule in respective format.

    6.0 ABBREVIATIONS

    6.1 SOP – Standard operating procedure
    6.2 RM – Raw material
    6.3 PM – Packing material
    6.4 QA – Quality assurance
    Get editable documentsView List

    3 comments: Post Yours! Read Comment Policy ▼

    1. How many minimum days require for mapping of control sample room

      ReplyDelete
    2. Dear Sir,
      30 Hottest Points(range 32-35 deg. C at summer)have been identified through mapping at 7 meter along with 01 coldest in an warehouse of ambient temp. (area 30000 sft.) where height is about 10 meters.
      How many data loggers I have to use for regular monitoring ?

      Md. Masudur Rahman

      ReplyDelete

    Please don't spam. Comments having links would not be published.


    Popular Categories ๐Ÿท️

    QA SOPs QC SOPs Micro SOPs HVAC Production SOPs Stores SOPs Checklists Maintenance SOPs HPLC Sterile GLP Validation Protocols Water System GDP Regulatory Maintenance Calibration Warning Letters Education B.Pharmacy Regulatory Updates
    Online Courses Salary Calculator
    Follow on Whatsapp


    Certificate Courses ๐ŸŽ–️

    Pharmaceutical Courses

    Follow Pharmaguideline


    DOCUMENTS ๐Ÿ“‹

    PHARMACEUTICAL DOCUMENTS




    Editable Pharmaceutical Documents in MS-Word Format. Ready to use SOPs, Protocols, Master Plans, Manuals and more...

    View


    adsbypg


    GET APP FOR NEWS UPDATES


    Android App