HVAC System Validation

Procedure for validation of HVAC system and details of tests in pharmaceutical industry: Air Flow Pattern, Air Flow Velocity & Change Per Hour, Filter Leak Test, Particles Count, Viable Monitoring, Filter Integrity Test ( DOP/PAO Test), Pressure Difference, Recovery, Temperature and Humidity Uniformity Test and Fresh Air Determination.

Heating Ventilation and Air Conditioning System (HVAC) Validation Tests

HVAC system validation is required for pharmaceutical cleanroom validation. The sterile area is validated through the following tests.

1.0 Air Flow Pattern

1.1 Take the titanium tetrachloride stick.
1.2 Burn the stick.
1.3 Place the burning stick in front of running Air Handling Unit (AHU).
1.4 Observed the flow of air with the help of smock distribution in the room.
1.5 Make chart diagram of the flow of air in the room for each room.

2.0 Air Flow Velocity And Change Per Hour

HVAC System Validation in Pharmaceutical
2.1 Scan the area of the HEPA Filter, with the anemometer probe, 6 inches from the filter face.
2.2 For the case of the experiment, divide the area of the HEPA Filter into four equal, hypothetical grids.
2.3 Record the velocity readings taken at the center of the grids, and at the junction of dividing lines (center of HEPA Filter) in 5.5.
2.4 Calculate the Average Velocity (V in feet per minute) as :
      V = (V1+V2+V3+V4)    -------- (Eq.1)
                          4
Vi = Velocity observation at each point
2.5 Measure the dimensions of each air inlet i.e. HEPA Filter, in feet and record it.
2.6 Calculate the Area (A in square feet) of each Air inlet as a product of the length and the width as :
      A = l x w    -------- (Eq.2)
      where l = length of inlet
               w = width of inlet
2.7 Calculate the Total Air Volume (T in cubic feet per minute) supplied in each zone, by using the formula :
      T = A x V   -------- (Eq.3)
      where A = Area of particular Air inlet in square feet
                V = Average air velocity at particular air inlet in feet per minute
2.8 Calculate the total volume of the room by multiplying the length of the room, the breath of the room and height of the room.
      Volume = L x B x H
2.9 Total air change is divided by the total volume of the room will give the air change per hour. Fill the record in the form.

3.0 Filter Leak Test

3.1 Place the velometer at the front of the AHU unit.
3.2 Check the velocity of air to all corner of the AHU. The air velocity should be within the higher limit of the HEPA filter.
3.3 If there is air velocity is more than higher limit changes the gas cut to prevent the air leakage.

4.0 Particles Count

4.1 On the air system before one hour of test operation. Take the suitable particle counter and operate it to check the particles in the room at non-working operation.
4.2 Collect the information from the particle counter and fill them in the format.
4.3 Operate the particle counter when work is on progress in the area. The particles should be count when more than one hour of work has been progressed in the area. Record the data in the format.
4.4 Operate the particle counter for all the room maintaining grade A, grade B, grade C & grade D.

5.0 Viable Monitoring

5.1 Expose Plate Count Agar and Saboraud Dextrose Agar media plates in sterile manufacturing area (Fabrication, Vial Filling, Vial Sealing & Sterile passage) as per location plan is given on the back of the paper sheet. Similarly expose the plates in Change Room II and III and De-gowning I twice in a week and once in a week in Vial Washing, Bung Washing and Component Preparation.
5.2 Monitor the microbial load on the surface of the sterile manufacturing area by swab sampling and testing follow the SOP. Carry out swab sampling daily in Vial Filling, Vial Sealing, Sterile Buffer and Blending III; and twice in a week in Sterile Passage, Change Room II, Change Room III and De-gowning I. Similarly carry out the swab sampling once in a week in Change Room I, Degowning II, Vial Washing, Bung Washing and component preparation. Record the results.
5.3 Place the media strips or Petri dishes in the air sampler on operating the air sampler as per the standard operating procedure of the equipment.
5.4 Record the data in the format.
5.5 Monitor the microbial load on the surface of hand gloves of the operators daily once in each working shift at random during activity follow the SOP and record the result in HVAC Documents. Record the data in the format.
5.6 In case of repeated failure during two observations the corrective action shall immediately be planned and implemented.
5.7 Monitor the critical functions of the HVAC system, Water System and personnel's behaviour in sterile and investigate the cause of adverse results immediately after observation.

6.0 Filter Integrity Test ( DOP / PAO Test for HVAC)

6.1 Generate DOP or PAO Aerosol using Aerosol generator, by subjecting DOP/PAO to 20 psi air pressure. Direct test aerosol at the supply duct in the Air Handling System.
6.2 Switch the photometer "ON" and allow to stabilize for five minutes.
6.3 Ensure that 100 % upstream concentration is achieved at all the terminal HEPA filters.
6.4 Scan the filter matrix and perimeter by passing the receptor probe 1 inch from the filter surface, in overlapping strokes traversing at approximately 10 FPM to check for leaks, if any.
6.5 Test all the HEPA filters as per the above steps and record the observations in the format.

7.0 Pressure Difference

7.1 Attach all concerning room (Under Test) to the manometer which is attached to the wall of the adjacent area.
7.2 On the air system inside the tested area and wait to stabilize the pressure in the area.
7.3 Observed the pressure difference from all room and from room to room.
7.4 Record the data in the format.

8.0 Recovery (Temperature & Humidity)

8.1 Off the HVAC system and checked the humidity of the area using a hygrometer.
8.2 If the humidity of the area within in specification. Increase the humidity by spraying hot water in the area up to 75%.
8.3 Wait to stabilize the humidity in the area about 75%.
8.4 Operate the HVAC system and note the time. Wait to stabilize the humidity in the area within the specification limit.
8.5 Note and record the time in the format.
8.6 For the recovery test increase the temperature of the area by using hot air blower in the area and increase the temperature 40C.
8.7 Operate the HVAC system and note the time. Wait to stabilize the temperature in the area within the specification limit.
8.8 Note and record the time in the format.

9.0 Temperature and Humidity Uniformity Test

9.1  Place the calibrated thermometer on a different location.
9.2  Operate the HVAC system and note the time. Wait to stabilize the temperature in the area within the specification limit.
9.3  Check and record the temperature of the area in format.
9.4  Place the calibrated hygrometer on a different location.
9.5  Operate the HVAC system and note the time. Wait to stabilize the humidity in the area within the specification limit.
9.6  Check and record the temperature of the area in format.

10.0 Fresh Air Determination

10.1 On the concerned AHU and wait to stabilize the air pressure in the room.
10.2 On the fresh air dumper for fresh air and observed and calculate the intake air by the dumper in the room. Observed and calculate the total air change in the room.
10.3 The intake fresh air is divided by the total air change in the room and multiply by 100 to calculate the % fresh air intake on each cycle by the HVAC system in the tested room.
10.4 Record the data in the performance format record.





Ankur Choudhary is India's first professional pharmaceutical blogger, author and founder of pharmaguideline.com, a widely-read pharmaceutical blog since 2008. Sign-up for the free email updates for your daily dose of pharmaceutical tips.
.moc.enilediugamrahp@ofni :liamENeed Help: Ask Question


34 comments: Post Yours! Read Comment Policy ▼

  1. Replies
    1. For new api facility how many days Ahu validation required. Normally 3 days all persons are doing. Can u tell which guidelines it was telling

      Delete
  2. Nice one And useful

    ReplyDelete
  3. kindly give the video clip for more understanding..
    like how we done hvac validation

    ReplyDelete
  4. good..really valuable sharing and helpful...

    ReplyDelete
  5. definitely it is worth full sharing

    ReplyDelete
  6. Good one, however "Acceptance Criterias" are missing.

    ReplyDelete
  7. why we use fresh air in each cycle at pharma industry and what is range generally use.

    ReplyDelete
    Replies
    1. Its 10% fresh air used in Pharma and the purpose behind is good ventilation and air change as per ACPH

      Delete
  8. thanq very much

    ReplyDelete
  9. Can u mention the stability chamber PQ challange test connected with BMS and Audit Trail system

    ReplyDelete
  10. in fresh air determination test
    which one is intake air and which one air change per hour considered for % determination of fresh air
    designed either actually calculate during normal operation without fresh air damper opened.
    dear sir please clear.

    ReplyDelete
  11. Hello sir
    My question is:- what is the limits of Non Viable particle Count as per WHO Guideline.

    ReplyDelete
  12. how to download WHO guideline.

    ReplyDelete
  13. THANK you Sir for sharing such an USEFULL information

    ReplyDelete
  14. good explanation on every topic what ever it is...great to have such kind of guidelines

    ReplyDelete
  15. Nice content.. please share guidelines also

    ReplyDelete
  16. Hi dears, I am help your.
    I am interested in, How caunt Laminar Flow Cabinets Particle Counting (At Rest, in operational)
    Thanks for advance

    ReplyDelete
  17. Neat and Straight forward

    ReplyDelete
  18. What is re qualifications frequency of AHU as per ISO and WHO

    ReplyDelete
  19. Extra ordinary explanation
    Thanks for sharing If possible share video clips

    ReplyDelete

Please don't spam. Comments having links would not be published.


Popular Categories

QA SOPs QC SOPs Micro SOPs HVAC Production SOPs Stores SOPs Checklists Maintenance SOPs HPLC Sterile GLP Validation Protocols Water System GDP Regulatory Maintenance Calibration Warning Letters Education B.Pharmacy
Online Courses


Follow Pharmaguideline


DOCUMENTS

PHARMACEUTICAL DOCUMENTS




Editable Pharmaceutical Documents in MS-Word Format. Ready to use SOPs, Protocols, Master Plans, Manuals and more...

View


adsbypg


Recent Posts